Performance Evaluation of Silica gel /water Adsorption Cooling Unit

Document Type : Original Article

Authors

1 1Mech. Power Eng. Dep., Faculty of Eng., Tanta University, Egypt

2 Mech. Eng. Dep., Faculty of Eng., Kafr elsheikh University, Egypt

Abstract

In the present work, an experimental study of adsorption refrigeration unit with modified adsorption bed is obtained. Silica gel and water are used as a working pair in the adsorption refrigeration unit. Hot air is used for Silica gel regeneration. The effect of evaporator pressure, evaporator inlet water temperature, initial Silica gel temperature, and hot air regeneration temperature and mass flow rate on the unit coefficient of performance is studied.  It has been found that increase of hot air regeneration temperature and inlet evaporator temperature increases the unit refrigeration capacity and coefficient of performance. On the other hand, a decrease of Silica gel temperature and evaporator pressure increases the unit refrigeration capacity and coefficient of performance. The results confirm that this kind of adsorption chiller is an effective refrigerating machine, it can be used  for air conditioning or producing chilling water since it make a reduction in the chilling water temperature more than 10ºC in 3 minutes. In addition the present unit with its novel adsorber gives higher coefficient of performance than that was obtained from the similar previous models

Keywords